Report Findings
Door Frame
Check: Splits / Damage

Fire Seals
(Flat)
Check: Damage / Paint



Smoke Seals
(Brushes or Fins)
Check: Damage / Paint


Door Leaf
Check: Holes/Splits/Damage

Handle Furniture
Check: Functional


Lockset/Latch
Check: Functional


Push Plates/Kick Plates
Check: Damage / Missing Screws


Bolt
Check: Functional / Missing Screws


Signage *Correct Sign
Check: Damage/Worn/Screws *Ideal Height 1500 to 2000mm

Edge / Face Protectors
Check: Damage


Glazing and Installation
Check: Installation / Damage
BSEN 1363 / 1364 / 1634



Panic/Emergency Set
Check: Functional / Damage


Air Transfer (Grille/Spy Viewer)
Check: Blockages / Fire Rating


Letter Box
Check: Functional
BSEN 1634-1 BS476-22


Door Closer/Floor Spring
Power Rating EN3 >=



Hinges or Pivots
Damage


Hold Open Device/Wall Interface
Check: Functional
BSEN 1155


Door to Frame Gaps (2-4mm)



Threshold Seal and Gap
(3mm Max FD30s)
(10mm Max FD30)

Other Components